Charging
Cycle Applications: Limit initial current
to 900mA. Charge until battery voltage (under charge) reaches 7.20 to 7.35
volts at 68º F (20º C). Hold at 7.20 to 7.35 volts until current drops to
approximately 45mA. Battery is fully charged under these conditions, and
charger should either be disconnected or switched to "float" voltage.
"Float" or "Stand-by Service": Hold battery
across constant voltage source of 6.75 to 6.90 volts continuously. When
held at this voltage, the battery will seek its own current level and
maintain itself in a fully charged condition. |