Charging
Cycle Applications: Limit
initial current to 440mA. Charge until battery voltage (under charge)
reaches 14.40 to 14.70 volts at 68� F (20� C). Hold at 14.40 to 14.70
volts until current drops to approximately 22mA. Battery is fully charged
under these conditions, and charger should either be disconnected or
switched to "float" voltage.
"Float" or "Stand-by
Service": Hold battery across constant voltage source of 13.50 to 13.80
volts continuously. When held at this voltage, the battery will seek its
own current level and maintain itself in a fully charged condition.
|